OT Laminar Air flow Manufacturers in Chennai

We are the leading company manufacturer & supplier of quality (OT) Operation Theatre Laminar Flow in Chennai.

OT laminar air flow

  • • The operating theatre ceiling is the most important part of a hospital ventilation system. Also called UCVS (Ultra Clean Ventilation System), these sophisticated systems are actually a combination of a variety of elements, including gas tight welded pressure chambers, air filter housings or filter grids, HEPA filters, priming illumination and air diffusers.
  • • Laminar Flow Ceiling for Operating Theatres
  • • to produce a germ- and particle lean area through an unidirectional air flow.
  • • The system is specially designed and suited for the use in Operating Theatres.
  • • The requirements according to ISO 14644 Standard and NABH Guidelines

Pressure Chamber

  • • Air sealed pressure chamber, made out of IS 304 Grade stainless steel 1.2mm thick Sheet
  • • Smooth inner surfaces, therefore easy to clean and disinfect during filter changes
  • • Special frame system for the integration of the filter frames, the pressure chamber, all required receptacles of the surrounding air flow stabilizers made out of anodized Aluminum.
  • • Openings for the supply duct connections
  • • Air sealed housing for the integration of the stand of the O.T. light and openings for the service of the O.T. light
  • • Aerosol port
  • • Port for pressure drop measurement
  • • Supply air connections as flange made out of IS 304 Grade stainless steel 1.2mm thick sheet
  • • Lateral attached, air sealed, disinfectant resistant varnished with connection flange for external duct installation.

Diffuser- Frame

  • • Frame made out of anodized Aluminum profile for the placement of the CG-Diffuser and has rails for the easy and seamless placement of the false sealing or other connecting equipment.
  • • The Aluminum profile is prepared for the integration of the sterile field and O.T.-illumination, when combined with the optional rail system for the O.T. illumination.

HEPA Filters

  • • Integrated HEPA Filter-Cells with a frame made out of galvanized sheet steel
  • • Optimized standard dimensions
  • • Extremely high filter surface for low initial pressure drops
  • • EPDM profile gasket
  • • Change of filters to the clean side

Sterile Air Diffuser CG

  • • Transparent diffuser with double layer micro mesh, made out of specialized textile
  • • Assembly and disassembly without screws or tools
  • • Air-flow optimized frame made out of Aluminum profile
  • • Pass through of the stand of the O.T. light
  • • Whole construction to the clean side smooth and without screws

Test port for LAF testing

  • • Mounted outside of the aluminum frame system with test connection for DEHS testing and pressure drop, varnished RAL 9016.
  • • Filter surface per m² face area 18,5 m²
  • • Norms: DIN 1946-4

No. Property POT 2408 POT 2406 POT 1806
1 Airflow Volume 4760 m³/h 3570 m³/h 277 m³/h
2 Outer Dimension W 2400 x D 2400 mm W 2400 x D 1800 mm W 1800 x D 1800 mm
3 Height of the Plenum Box 450 mm 450 mm 450 mm
4 HEPA Filter Area W 2290 x D 2290 mm W 2290 x D 1710 mm W 1710 x D 1710 mm
5 Average Velocity 0.25 m/sec 0.25 m/sec 0.25 m/sec
6 No of HEPA Filters 8 Nos 6 Nos 4 Nos
7 HEPA Filter Class as per EN 1822 H13 H13 H13
8 Initial Pressure Drop 160 Pa 160 Pa 160 Pa
9 Final Pressure Drop 600 Pa 600 Pa 600 Pa
10 No for Collar 6 Nos 4 Nos 4 Nos
11 Height of Available Ceiling Space (minimum requirement) 550 mm